Calcometry

Calculadora de queda de tensão

Ao usar nossas calculadoras, você concorda com nossos Termos de uso (English).

Simple DC drop in copper wire — round-trip length, not electrical code.

Cabo de cobre

Queda de tensão

3.36 V

Wire resistance ≈ 0.336 Ω

Resistência (ida e volta)
0.336 Ω

Calculadoras relacionadas

Wire voltage drop

Voltage drop is the loss across wire resistance: V = I × R. For DC copper wire, resistance depends on length (round trip), cross-sectional area, and resistivity (ρ ≈ 1.68×10⁻⁸ Ω·m for copper at room temperature).

Long runs, thin wire, and high current increase drop — motors and inverters may underperform if supply voltage sags. National electrical codes specify maximum drops for branch circuits; this is a quick estimate, not a NEC compliance check.

Example: 10 A through 25 m one-way (50 m loop) of 2.5 mm² copper drops about 3.4 V. Size wire for your acceptable drop and local code.

Round-trip length matters: current travels out and back, so a 25 m one-way run uses 50 m of conductor in the resistance calculation. Underestimating length is a common cause of surprise voltage sag on solar and RV installs.

Thicker wire (larger mm² or lower AWG number) lowers resistance and drop. If drop exceeds your device's minimum input voltage, step up wire size or move the power source closer.

Worked example with defaults: 10 A, 25 m one-way, 2.5 mm² cross-section → about 3.4 V drop on copper at room temperature. On a 12 V system that is roughly 28% of supply — often too high for sensitive loads.

NEC guidance often cites 3% maximum drop on branch circuits and 5% total from service to load — on a 12 V solar system, 3% is only 0.36 V, stricter than many appliance specs. Express drop as a percent of supply to compare against code-style limits. Three percent of 12 V is only 0.36 V — express drop as percent of supply when comparing against inverter low-voltage disconnect thresholds.

AWG wire sizes map to cross-section in mm²: 14 AWG ≈ 2.08 mm², 12 AWG ≈ 3.31 mm². If your spool is labeled AWG but the form asks mm², convert before entering — undersized wire is a common cause of nuisance undervoltage faults. 14 AWG ≈ 2.08 mm² and 12 AWG ≈ 3.31 mm² — convert spool labels before entering cross-section if your reel shows AWG only.

Aluminum conductors have higher resistivity than copper (~1.68 vs ~2.82 × 10⁻⁸ Ω·m at room temp). This tool assumes copper; swapping aluminum without adjusting resistivity underestimates drop — size aluminum one AWG larger than copper charts suggest. Aluminum needs roughly one AWG size larger than copper for similar drop — this copper model underestimates loss on aluminum conductors.

Perguntas frequentes

Is this AC or DC?

DC resistive estimate. AC lines also have reactance; use this for low-voltage DC, solar, or bench wiring sanity checks only.

Does this replace an electrician?

No. Verify wire sizing with local electrical code and licensed professionals for permanent installations.

Why use one-way length instead of total loop?

The form asks for one-way distance; the calculator doubles it internally for the round-trip path electrons follow through supply and return conductors.